| FWE03DATN5V1L (Archived) | FWE04DATN5V1L (Archived) | FWE05DATN5V1L (Archived) | FWE06DATN5V1L (Archived) | FWE07DATN5V1L (Archived) | FWE08DATN5V1L (Archived) | FWE10DATN5V1L (Archived) | FWE11DATN5V1L (Archived) | |||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Wydajność chłodnicza (standardowe warunki) | Użyteczna wydajność, inst. 2-przewod. | Prędkość wentylatora 1 | kW | 1.95 | 2.11 | 2.30 | 1.02 | 1.48 | 1.95 | 2.11 | 2.30 | |
| Prędkość wentylatora 6 | kW | 3.22 | 4.28 | 4.59 | 2.56 | 3.14 | 3.22 | 4.28 | 4.59 | |||
| Niska | kW | 1.95 | 2.11 | 2.30 | 1.02 | 1.48 | 1.95 | 2.11 | 2.30 | |||
| Wysoka | kW | 3.22 | 4.28 | 4.59 | 2.56 | 3.14 | 3.22 | 4.28 | 4.59 | |||
| Wydajność całkowita, inst. 2-przewod. | Prędkość wentylatora 1 | kW | 1.22 | 1.21 | 1.33 | 1.24 | 1.80 | 2.38 | 2.57 | 2.81 | ||
| Prędkość wentylatora 6 | kW | 3.12 | 3.83 | 3.92 | 5.22 | 5.60 | ||||||
| Niska | kW | 1.22 | 1.21 | 1.33 | 1.24 | 1.80 | 2.38 | 2.57 | 2.81 | |||
| Wysoka | kW | 1.77 | 2.06 | 2.58 | 3.12 | 3.83 | 3.92 | 5.22 | 5.60 | |||
| Wydajność grzewcza (standardowe warunki) | Wydajność, inst. 2-przewod. | Prędkość wentylatora 1 | kW | 1.55 | 1.53 | 1.67 | 1.52 | 2.26 | 2.94 | 3.36 | 3.68 | |
| Wydajność grzewcza (standardowe warunki)-=-Wydajność, inst. 2-przewod.-=-Prędkość wentylatora 6-=-kW | kW | 4.03 | 4.98 | 5.11 | 6.93 | 7.43 | ||||||
| Niska | kW | 1.55 | 1.53 | 1.67 | 1.52 | 2.26 | 2.94 | 3.36 | 3.68 | |||
| Wysoka | kW | 2.28 | 2.65 | 3.33 | 4.03 | 4.98 | 5.11 | 6.92 | 7.43 | |||
| Pobór mocy | Prędkość wentylatora 1 | kW | 0.03 | 0.03 | 0.03 | 0.04 | 0.04 | 0.03 | 0.03 | 0.03 | ||
| Prędkość wentylatora 6 | kW | 0.062 | 0.065 | 0.067 | 0.104 | 0.110 | ||||||
| Niska | kW | 0.03 | 0.03 | 0.03 | 0.04 | 0.04 | 0.03 | 0.03 | 0.03 | |||
| Wysoka | kW | 0.031 | 0.032 | 0.039 | 0.062 | 0.065 | 0.067 | 0.104 | 0.110 | |||
| Wymiary | Jednostka | Wysokość | mm | 200 | 200 | 200 | 200 | 200 | 200 | 200 | 200 | |
| Szerokość | mm | 797 | 797 | 797 | 997 | 1200 | 1200 | 1200 | 1200 | |||
| Głębokość | mm | 610 | 610 | 610 | 610 | 610 | 610 | 610 | 610 | |||
| Obudowa | Kolor | Metal | Metal | Metal | Metal | Metal | Metal | Metal | Metal | |||
| Wentylator | Natężenie przepł. pow. | Prędkość wentylatora 1 | m³/h | 235 | 226 | 242 | 289 | 335 | 396 | 436 | 489 | |
| Prędkość wentylatora 6 | m³/h | 676 | 820 | 725 | 1031 | 1115 | ||||||
| Przepływ powietrza | Niski | m³/h | 235 | 226 | 242 | 289 | 335 | 396 | 436 | 489 | ||
| Wysoki | m³/h | 365 | 385 | 488 | 676 | 820 | 725 | 1031 | 1115 | |||
| Spręż dyspozycyjny | Prędkość wentylatora 1 | Pa | 20 | 20 | 20 | 20 | 20 | 20 | 20 | 20 | ||
| Prędkość wentylatora 6 | Pa | 50 | 50 | 50 | 50 | 50 | ||||||
| Niska | Pa | 20 | 20 | 20 | 20 | 20 | 20 | 20 | 20 | |||
| Wysoka | Pa | 40 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | |||
| Całkowity poziom ciśnienia akustycznego | Prędkość wentylatora 1 | dBA | 33.0 | 33.0 | 33.0 | 30.0 | 31.0 | 31.0 | 38.0 | 40.0 | ||
| Prędkość wentylatora 6 | dBA | 50.0 | 50.0 | 50.0 | 57.0 | 59.0 | ||||||
| Niski | dBA | 32.0 | 33.0 | 32.0 | 30.0 | 31.0 | 31.0 | 38.0 | 40.0 | |||
| Wysoki | dBA | 42.0 | 44.0 | 50.0 | 50.0 | 50.0 | 50.0 | 57.0 | 59.0 | |||
| Przepływ wody | Chłodzenie | Prędkość wentylatora 1 | l/h | 219 | 218 | 238 | 225 | 324 | 423 | 457 | 500 | |
| Prędkość wentylatora 6 | l/h | 560 | 685 | 702 | 937 | 1005 | ||||||
| Niska | l/h | 219 | 218 | 238 | 225 | 324 | 423 | 457 | 500 | |||
| Wysoka | l/h | 316 | 368 | 461 | 560 | 685 | 702 | 937 | 1005 | |||
| Ogrzewanie | Prędkość wentylatora 1 | l/h | 136 | 134 | 147 | 133 | 199 | 259 | 296 | 324 | ||
| Prędkość wentylatora 6 | l/h | 354 | 438 | 449 | 610 | 654 | ||||||
| Niska | l/h | 136 | 134 | 147 | 133 | 199 | 259 | 296 | 324 | |||
| Wysoka | l/h | 201 | 233 | 293 | 354 | 438 | 449 | 610 | 654 | |||
| Spadek ciśnienia wody | Chłodzenie | Prędkość wentylatora 1 | kPa | 7 | 4 | 4 | 2 | 2 | 10 | 8 | 10 | |
| Prędkość wentylatora 6 | kPa | 10 | 19 | 20 | 32 | 36 | ||||||
| Niski | kPa | 7 | 4 | 4 | 2 | 2 | 10 | 8 | 10 | |||
| Wysoki | kPa | 12 | 11 | 15 | 10 | 19 | 20 | 32 | 36 | |||
| Ogrzewanie | Prędkość wentylatora 1 | kPa | 3 | 2 | 1 | 2 | 1 | 1 | 4 | 4 | ||
| Prędkość wentylatora 6 | kPa | 6 | 5 | 12 | 14 | |||||||
| Niski | kPa | 3 | 2 | 1 | 2 | 1 | 1 | 4 | 4 | |||
| Wysoki | kPa | 5 | 4 | 5 | 3 | 6 | 5 | 12 | 14 | |||
| Dopuszczalna temperatura wody | Chłodzenie | Min. | °C | 5 | 5 | 5 | 5 | 5 | 5 | 5 | 5 | |
| Maks. | °C | 80.0 | 80.0 | 80.0 | 80.0 | 80.0 | ||||||
| Ogrzewanie | Min. | °C | 5.00 | 5.00 | 5.00 | 5.00 | 5.00 | 5.00 | 5.00 | 5.00 | ||
| Maks. | °C | 80.000 | 80.000 | 80.000 | 80.000 | 80.000 | 80.000 | 80.000 | 80.000 | |||
| Połączenia instalacji | Woda | Wlot | 3/4" | 3/4" | 3/4" | 3/4" | 3/4" | 3/4" | 3/4" | 3/4" | ||
| Wylot | 3/4" | 3/4" | 3/4" | 3/4" | 3/4" | 3/4" | 3/4" | 3/4" | ||||
| Spust | Śr. zew. | mm | 17.3 | 17.3 | 17.3 | 17.3 | 17.3 | 17.3 | 17.3 | 17.3 | ||
| Standardowe akcesoria | Odbiornik spustowy | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | |||
| Instrukcja obsługi i instalacji | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | ||||
| Torebka ze śrubami | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | ||||
| Zasilanie | Typ | 220-240 / 1 / 50 | 220-240 / 1 / 50 | 220-240 / 1 / 50 | 220-240 / 1 / 50 | 220-240 / 1 / 50 | 220-240 / 1 / 50 | 220-240 / 1 / 50 | 220-240 / 1 / 50 | |||
| Zasilanie energią elektryczną | liczba faz | 1~ | 1~ | 1~ | 1~ | 1~ | 1~ | 1~ | 1~ | |||
| Zasilanie | Częstotliwość | Hz | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | ||
| Napięcie | V | 220-240 | 220-240 | 220-240 | 220-240 | 220-240 | 220-240 | 220-240 | 220-240 | |||
| Pobór prądu | Prędkość wentylatora 1 | A | 0.01 | 0.01 | 0.01 | 0.02 | 0.02 | 0.02 | 0.01 | 0.03 | ||
| Prędkość wentylatora 6 | A | 0.03 | 0.02 | 0.02 | 0.04 | 0.05 | ||||||
| Prąd wejściowy | Niski | A | 0.01 | 0.01 | 0.01 | 0.02 | 0.02 | 0.02 | 0.01 | 0.03 | ||
| Wysoki | A | 0.01 | 0.01 | 0.02 | 0.03 | 0.02 | 0.02 | 0.04 | 0.05 | |||
| Uwagi | (1) - Temperatura wlotowa/wylotowa wody 7/12 °C; temperatura wlotowa powietrza 27°C DB 19°C WB | (1) - Temperatura wlotowa/wylotowa wody 7/12 °C; temperatura wlotowa powietrza 27°C DB 19°C WB | (1) - Temperatura wlotowa/wylotowa wody 7/12 °C; temperatura wlotowa powietrza 27°C DB 19°C WB | (1) - Temperatura wlotowa/wylotowa wody 7/12 °C; temperatura wlotowa powietrza 27°C DB 19°C WB | (1) - Temperatura wlotowa/wylotowa wody 7/12 °C; temperatura wlotowa powietrza 27°C DB 19°C WB | (1) - Temperatura wlotowa/wylotowa wody 7/12 °C; temperatura wlotowa powietrza 27°C DB 19°C WB | (1) - Temperatura wlotowa/wylotowa wody 7/12 °C; temperatura wlotowa powietrza 27°C DB 19°C WB | (1) - Temperatura wlotowa/wylotowa wody 7/12 °C; temperatura wlotowa powietrza 27°C DB 19°C WB | ||||
| (2) - Ogrzewanie: temp. wewn. 20°CDB, 15°CWB; temp. wody na wlocie 45°C, spadek temperatury wody o 5K. | (2) - Ogrzewanie: temp. wewn. 20°CDB, 15°CWB; temp. wody na wlocie 45°C, spadek temperatury wody o 5K. | (2) - Ogrzewanie: temp. wewn. 20°CDB, 15°CWB; temp. wody na wlocie 45°C, spadek temperatury wody o 5K. | (2) - Ogrzewanie: temp. wewn. 20°CDB, 15°CWB; temp. wody na wlocie 45°C, spadek temperatury wody o 5K. | (2) - Ogrzewanie: temp. wewn. 20°CDB, 15°CWB; temp. wody na wlocie 45°C, spadek temperatury wody o 5K. | (2) - Ogrzewanie: temp. wewn. 20°CDB, 15°CWB; temp. wody na wlocie 45°C, spadek temperatury wody o 5K. | (2) - Ogrzewanie: temp. wewn. 20°CDB, 15°CWB; temp. wody na wlocie 45°C, spadek temperatury wody o 5K. | (2) - Ogrzewanie: temp. wewn. 20°CDB, 15°CWB; temp. wody na wlocie 45°C, spadek temperatury wody o 5K. | |||||
| (3) - Ogrzewanie: temp. wewn. 20°CDB, 15°CWB; temp. wody na wlocie 65°C, spadek temperatury wody o 10K. | (3) - Ogrzewanie: temp. wewn. 20°CDB, 15°CWB; temp. wody na wlocie 65°C, spadek temperatury wody o 10K. | (3) - Ogrzewanie: temp. wewn. 20°CDB, 15°CWB; temp. wody na wlocie 65°C, spadek temperatury wody o 10K. | (3) - Ogrzewanie: temp. wewn. 20°CDB, 15°CWB; temp. wody na wlocie 65°C, spadek temperatury wody o 10K. | (3) - Ogrzewanie: temp. wewn. 20°CDB, 15°CWB; temp. wody na wlocie 65°C, spadek temperatury wody o 10K. | (3) - Ogrzewanie: temp. wewn. 20°CDB, 15°CWB; temp. wody na wlocie 65°C, spadek temperatury wody o 10K. | (3) - Ogrzewanie: temp. wewn. 20°CDB, 15°CWB; temp. wody na wlocie 65°C, spadek temperatury wody o 10K. | (3) - Ogrzewanie: temp. wewn. 20°CDB, 15°CWB; temp. wody na wlocie 65°C, spadek temperatury wody o 10K. | |||||